Possible measurements:
Measurement of earthing resistance
measurement range to IEC61557 - 5:
0,50 Ω...1,99 kΩ for Un=50 V;
0,68 Ω...1,99 kΩ for Un=25 V;
Range | Resolution | Accuracy |
0,00...9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0...99,9 Ω | 0,1 Ω | |
100...999 Ω | 1 Ω | |
1,00k...1,99 kΩ | 0,01 kΩ |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable <25 V AC or <50 V AC,
• frequency of measurement current: 125 Hz
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0...100 V | 1 V | ±(2% m.v. + 3 digits) |
• measurement for DC and AC 45…65 Hz
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0...999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 3 digits) |
1,00k...9,99 kΩ | 0,01 kΩ | |
10,0k...50,0 kΩ | 0,1 kΩ |
Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 - 4: 0,13 Ω...199 Ω
Range | Resolution | Accuracy |
0,00...9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0...99,9 Ω | 0,1 Ω | |
100...199 Ω | 1 Ω |
Electric security:
Rated operational conditions:
Other technical data: