Hi-Trans Primary Injection test system HTPI is a high current unit consisting of a control unit and one or two external power transformers,
that can be easily taken in proximity of bus-bars, thus keeping to the minimum the test cable length.
• Current and power range selection.
• Coarse and fine output adjustment.
• Current metering: by 3 and half digit instrument,
• Adjustable voltage output characteristics:
• Range: 0 to 270 V AC;
•Current output: 0 to 5000A.
|
Sl. No. |
Specification |
Rating / Ranges/ Type |
|
01. |
Primary Injection Kit |
5000Amps , 10 KVA |
|
02. |
Current Range : |
0 – 5000 Amps |
|
03. |
Output Voltage - |
5000 A – 2 Volt |
|
04. |
Input Supply Voltage |
230 Volts AC 50 Hz |
|
05. |
Output Current Resolution |
1.5 Amp |
|
06. |
Display |
LED type |
|
07. |
Burden Capacity |
10 KVA |
|
07. |
Timer Range |
0.0001sec to 9999 sec, Accuracy :- ± 0.05% |
|
08. |
Display Accuracy |
± 1.5% of rdg. ± 2 digit |
|
09. |
Duty Cycle |
5 Min ON & 15 Min OFF at Load current – |
|
10. |
Operation |
Manual Operation |
|
11. |
Timer |
With Trip Circuit ( NC – C – NO ) |
|
12. |
Protection |
The equipment should be well protected by circuit breakers, fuses to prevent overheating and damage. |
|
13. |
Transportation |
The test set should be wheel mounted for easy transportation. |
|
14. |
Accessories |
Set of 5000A current lead set with Lugs & conectors ( Both Side ) (240 sq. mm. X 5) 1200 sq mm. cotton braded Multi strand copper cable , Cable Length – 2 X 2 Meter Power Supply cord One set of spare fuse Inter Connecting Cable Operation manual Wheel mounted transportation Complete Kit in two Unit – 1 – Control Unit 2 – Loading Unit Calibration certificate
|